TOLL FREE: 1800 2331846
News & Events Customer Service Contact Us
HomeAbout UsProductsNew LaunchesQualityResearchInfrastructureClientsCareersBusiness Opportunity
Single Phasing Preventers (SPP)
Motor Guard Relay
Pumppro
Liquid Level Controller
Single Phase & Three Phase Electronic Starters
Overload relay
Earth Leakage Relay(ELR)
Industrial Energy Saving Tube Fittings & Ballasts
Industrial Lighting Fixtures
Automatic Light Control Switch (Auto photo)
Servo Voltage Stabilizer
Digital Time Switch
 
Temperature Controller /
Temperature Indicator
Analog Timers
Counters
Panel Meters
Whitez Modular Switches
Servo Voltage Regulators (SCVR)
System Monitoring Relays
Digital Timer
Phase Failure Relays / Motor-Pump Protection Relays
It is basically current sensing single phasing preventer which gives total protection to three phase ac electric motor. The basic principle of operation is of sensing negative sequence current components and it trips electric motor starter as soon as it exceeds the dangerous level. This model offers protections upto motor terminals & is undefective to the motor back e.m.f. it is available in two models namely mgr & mgr-c. Both models are bascially same with slight difference in features like under/over voltage protection and inverse time current charactersitic setting.
These models offer total protection against single phasing on supply side as well as motor side. Overloading (inversely time current characteristics) reverse supply, current unbalance & low/high voltage, auto /manual reset provision etc. Is provided. The enclosure is made from high impact polysterene moulded with nylon moulded connection strip. It is available upto 200 amps. Green led indicates spp healthy condition and red led indicates overloading condition. Both models offer single phasing protection even if motor is on no load. It weighs 750 grams approx. And it's overall dimensions are 140 x 100 x 95mm.
 

MGR/MEG-C, current sensing SPP offers single phasing, reverse phasing, low/high voltage and overload protection with slight different features of inverse trip time current characteristics.

MGR: Fixed inverse trip time current characteristic (2 sec. std) which is factory set.

MGR-C: Variable inverse trip time current characteristic (from 2 sec. to 10 sec)

MGR V, voltage and current sensing SPP offers single phasing, reverse phasing and overload protections with fixed price trip time current characteristic (2 sec. std) which is factor set.

 

Technical Specifications

 
System voltage:

415 V +/- 20%, 3 @, 50 Hz

Auxiliary supply:

415 /230/110 V AC, 50 Hz

Output contact rating:

1 C/O potential free, 6 A resistive at 230 V or 1 A at 415 V at 0.5 PF

Trip time delay

 
For single phasing and reverse phasing:

4 to 7 seconds

For overload:

As per inverse time current characteristics

 
MGR/MGR-V:

2 sec. std (which is factory set)

MGR-C: 2 sec to 10 sec (adjustable)

For MGR/MGR-C model

 
High voltage cut-off/cut in:

500V +/- 5V/470 +/- 5V

Low voltage cut-off/cut in:

320V +/- 5V/340 +/- 5V

Reset:

Auto/manual/remote by external push button

Power consumption:

3 VA

Recommended wiring: 1.0 sq. mm
H.V. Test:

2 KV AC, 50 Hz for 1 minute between mounting plate and any terminal

Humidity:

Up to 95% RH

Enclosure:

High impact polystyrene molded with nylon molded connection trip

Fail safe:

Relay is energized in healthy conditions and trips in faulty conditions

Life expectancy:

0.5 x 10 5 operations

Indication for MGR/MGR-C:

Power On, low volt, SPP faulty, high volt, overloads

 
MGR-V:

Current SPP healthy, voltage SPP faulty, overload

Dimension:
Overall:

140x100x95 mm

Mounting:

129 x 74 mm

CT Dimension
Inbuilt:

16 mm ID

Separate:

31 mm ID

Weight: 750 gms (approx)
 
 

Terminal Marking

 

1 & 2 - Relay contacts for annunciation (NC)

2 & 3 - Relay contacts for tripping the starter (NO)

5 & 6 - Aux supply as marked on unit

4,7,8,9 - Dummy terminals

10 & 11 - Link for manual reset

11 & 12 - External reset push button (manual)

 

Instructions

 

Dotted line shown go through the two PVC pipes internal to the MGR unit

Relay contacts shown for the unit in healthy conditions

If starter dose not hold, interchange R & B (phase go through cts.)

 